 The Digital Ground Resistance Tester Model 4630 performs ground resistance and soil resistivity tests. This direct reading testers measures from 0 to 2000W, and is auto-ranging, so it automatically seeks outs the optimum measurement range. The Model 4630 is rugged, easy-to-use and is ideal for maintenance crews performing numerous tests. It exceeds mechanical and safety specifications for shock, vibration and drop tests called out in IEC standards. It is designed to reject high levels of interference, so it can be used under difficult conditions such as high stray currents that normally affect accuracy. The Model 4630 is powered by 9.6V, 3.5 Ah NiMH rechargeable batteries. A built-in recharge circuit, powered from 120/230V 50/60Hz line, also provides for testing while recharging. Features- Measures soil resistivity (4-Point) method
- Measures ground resistance (2- and 3-Point) Fall-of-Potential method
- Step voltage tests and touch potential measurements
- Auto-Ranging: automatically selects the optimum range
- Designed to reject high levels of noise interference
- Extremely simple to operate: connect - press - read
- LED on faceplate informs operator of high input noise, high auxiliary rodresistance and fault connections
- AC powered with rechargeable NiMH batteries
- Rugged, dustproof and rainproof field case
- Can also be used for continuity tests on bonding
- Color-coded terminals
| Electrical | | Range | 20Ω | 200Ω | 2000Ω | | Measurement Range | 0.00 to 19.99Ω | 20.0 to 199.9Ω | 200 to 1999Ω | | Resolution | 10mΩ | 100mΩ | 1Ω | | Open Voltage | < 42V peak | < 42V peak | < 42V peak | | Resistance Measurement Frequency | 128Hz square wave | 128Hz square wave | 128Hz square wave | | Test Current | 10mA | 1mA | 0.1mA | | Accuracy | + 2% of Reading + 1ct | + 2% of Reading + 1ct | + 2% of Reading + 3cts | Auxiliary Electrode InfluenceMax Res. in Current Circuit Max Res. in Voltage Circuit | 3kΩ 2000Ω | | 50kΩ 50kΩ | | Response Time | Approximately 4 to 8 seconds for a stabilized measurement | | Withstanding Voltage | 250V AC or 1000V DC | | Power Source | 120/230V 50/60Hz Rechargeable 9.6V, 3.5 Ah NiMH batteries | | Battery Life | 1800 15-second measurements; LO BAT indication on LCD | | Fuse Protection | 0.1A, 250V, 0.25 x 1.25"; 30kA Interrupt Capacity |
|